首页> 外文OA文献 >Directional earth fault relay operation in mutually coupled multiple circuit distribution lines
【2h】

Directional earth fault relay operation in mutually coupled multiple circuit distribution lines

机译:相互耦合的多回路配电线路中的定向接地故障继电器操作

摘要

Many of the power utilities around the world experienced spurious tripping of directional earth fault relays in their mesh distribution networks due to induced circulating currents. This circulating current is zero sequence and induced in the healthy circuit due to the zero sequence current flow resulting from a ground fault of a parallel circuit. This paper quantitatively discusses the effects of mutual coupling on earth fault protection of distribution systems. An actual spurious tripping event is analyzed to support the theory and to present options for improved resilience to spurious tripping.
机译:由于感应的循环电流,世界上许多电力公司都经历了其网状配电网络中定向接地故障继电器的误跳闸。该循环电流为零序,并且由于并联电路的接地故障导致的零序电流流动,在正常电路中感应出该循环电流。本文定量地讨论了互耦对配电系统接地故障保护的影响。分析了实际的虚假跳闸事件,以支持该理论并提出各种选项,以增强对虚假跳闸的恢复能力。