An inverse time admittance relay for fault detection in distribution networks containing DGs

机译:用于含DG的配电网故障检测的逆时导纳继电器

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

Isolation of a faulted segment, from either side of a fault, in a radial feeder that has several converter interfaced DGs is a challenging task when current sensing protective devices are employed. The protective device, even if it senses a downstream fault, may not operate if fault current level is low due to the current limiting operation of converters. In this paper, a new inverse type relay is introduced based on line admittance measurement to protect a distribution network, which has several converter interfaced DGs. The basic operation of this relay, its grading and reach settings are explained. Moreover a method is proposed to compensate the fault resistance such that the relay operation under this condition is reliable. Then designed relay performances are evaluated in a radial distribution network. The results are validated through PSCAD/EMTDC simulation and MATLAB calculations.
机译:当采用电流感测保护装置时,在具有多个转换器接口的DG的径向馈线中,从故障的两侧隔离故障段是一项艰巨的任务。由于转换器的限流操作,即使故障电流水平较低,该保护设备即使检测到下游故障也可能无法工作。本文介绍了一种基于线路导纳测量的新型反型继电器,以保护配电网,该配电网具有多个转换器接口的DG。解释了该继电器的基本操作,等级和范围设置。此外,提出了一种补偿故障电阻的方法,以使得在该条件下的继电器操作可靠。然后在径向分布网络中评估设计的继电器性能。通过PSCAD / EMTDC仿真和MATLAB计算验证了结果。