Condition assessment of power transformer onload tap changers using wavelet analysis and self-organizing map: field evaluation

机译:基于小波分析和自组织图的电力变压器有载分接开关状态评估:现场评估

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

An onload tap changer (OLTC) is the most maintenance intensive subassembly on a power transformer. Vibration monitoring is an effective technique that can be used to assess the condition of an OLTC nonintrusively. The authors have developed a condition monitoring system for common types of OLTCs that enables the condition of tap changer contacts and associated drive system to be inferred from vibration signals. A number of prototype systems have been installed onto OLTCs in distribution zone substations for field trials. Particular emphasis has been given to the detection of faults in a particular type of older tap changer that had been prone to a range of faults associated with the switching contacts and drive mechanism. For this type of tap changer, it has been shown to be possible to determine not only that the tap changer is aging but also to identify the particular part that is degrading.
机译:有载分接开关(OLTC)是电力变压器上维护最密集的子组件。振动监测是一种有效的技术,可用于非侵入性地评估OLTC的状况。作者已经开发了一种用于普通类型OLTC的状态监视系统,该系统能够从振动信号中推断出分接开关触点和相关驱动系统的状态。已在配电区变电站的OLTC上安装了许多原型系统,用于现场试验。已经特别强调了在特定类型的老式分接开关中的故障检测,该故障易于产生与开关触点和驱动机构相关的一系列故障。对于这种类型的分接开关,已经证明不仅可以确定分接开关是否老化,而且还可以识别正在退化的特定部件。

著录项

  • 作者

    Kang Pengju; Birtwhistle David;

  • 作者单位
  • 年度 2003
  • 总页数
  • 原文格式 PDF
  • 正文语种 {"code":"en","name":"English","id":9}
  • 中图分类

相似文献

  • 外文文献
  • 中文文献
  • 专利
代理获取

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号