首页> 外文OA文献 >DC fault detection and location in meshed multi-terminal HVDC systems based on DC reactor voltage change rate
【2h】

DC fault detection and location in meshed multi-terminal HVDC systems based on DC reactor voltage change rate

机译:基于直流电抗器电压变化率的网状多端子HVDC系统中的直流故障检测和定位

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

The change rate of the DC reactor voltage with predefined protection voltage thresholds is proposed to provide fast and accurate DC fault detection in a meshed multi-terminal HVDC system. This is equivalent to the measurement of the second derivative of the DC current but has better robustness in terms of EMI noise immunization. In addition to fast DC fault detection, the proposed scheme can also accurately discriminate the faulty branch from the healthy ones in a meshed DC network by considering the voltage polarities and amplitudes of the two DC reactors connected to the same converter DC terminal. Fast fault detection leads to lower fault current stresses on DC circuit breakers and converter equipment. The proposed method requires no telecommunication, is independent of power flow direction, and is robust to fault resistance variation. Simulation of a meshed three-terminal HVDC system demonstrates the effectiveness of the proposed DC fault detection scheme.
机译:提出了具有预定义保护电压阈值的直流电抗器电压的变化率,以在网状多端子HVDC系统中提供快速,准确的直流故障检测。这等效于测量直流电流的二阶导数,但在EMI噪声免疫方面具有更好的鲁棒性。除了快速检测直流故障外,该方案还可以通过考虑连接到同一转换器直流端子的两个直流电抗器的电压极性和幅值,准确地将故障分支与网状直流网络中的正常分支区分开。快速故障检测可降低直流断路器和变流器设备上的故障电流应力。所提出的方法不需要电信,与潮流方向无关,并且对故障电阻变化具有鲁棒性。网格化的三端HVDC系统的仿真证明了所提出的DC故障检测方案的有效性。

著录项

  • 作者

    Li Rui; Xu Lie; Yao Liangzhong;

  • 作者单位
  • 年度 2016
  • 总页数
  • 原文格式 PDF
  • 正文语种 en
  • 中图分类
  • 入库时间 2022-08-20 20:46:01