首页> 外文OA文献 >Evaluating the impact of superconducting fault current limiters on distribution network protection schemes
【2h】

Evaluating the impact of superconducting fault current limiters on distribution network protection schemes

机译:评估超导故障限流器对配电网络保护方案的影响

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

Rising fault levels are becoming increasingly problematic in the UK distribution network, with large sections of the network operating near to its designed fault level capability. With the increase in penetration of distributed generation that is expected in the coming years, this situation is becoming more pressing. Traditional methods of dealing with the issue may not be appropriate - upgrading plant is expensive and disruptive, while network reconfiguration can compromise security of supply. Superconducting Fault Current Limiters (SFCLs) are emerging as a potential solution, with installations now taking place in several locations worldwide. The integration of an SFCL into a network involves a number of challenges, particularly concerning the coordination of protection systems. The operation of existing protection schemes may be compromised due to the increased resistance in the network during a fault (in the case of a resistive SFCL). Furthermore, the reduction in fault levels, although desirable, can have a detrimental impact on protection operating times. This paper will consider an existing medium voltage network in the UK, which incorporates distributed generation capacity. The performance of IDMT overcurrent and distance protection schemes will be examined when an SFCL is installed in this network. In particular, the increased operating time of overcurrent relays will be discussed along with grading implications. The impact on distance protection reach will also be examined. A variety of network operational scenarios including SFCL placement and fault conditions will be considered and compared. Recommendations will be made in terms of protection settings and SFCL placement in order to mitigate the aforementioned issues.
机译:在英国的配电网络中,不断上升的故障等级正变得越来越成问题,网络的大部分运行在其设计的故障等级能力附近。随着未来几年分布式发电普及率的提高,这种情况变得越来越紧迫。解决该问题的传统方法可能不适合-升级工厂非常昂贵且具有破坏性,而网络重新配置会损害供应的安全性。超导故障电流限制器(SFCL)逐渐成为一种潜在的解决方案,目前已在全球多个地点进行了安装。将SFCL集成到网络中涉及许多挑战,尤其是在保护系统的协调方面。由于故障期间网络中电阻的增加(在电阻性SFCL的情况下),可能会损害现有保护方案的操作。此外,故障水平的降低,尽管是所希望的,但是可能对保护工作时间产生不利影响。本文将考虑英国现有的中压网络,该网络具有分布式发电能力。当在该网络中安装了SFCL时,将检查IDMT过电流和距离保护方案的性能。特别是,将讨论过电流继电器增加的工作时间以及分级含义。也将检查对距离保护范围的影响。将考虑并比较各种网络操作方案,包括SFCL放置和故障情况。将针对保护设置和SFCL放置提出建议,以减轻上述问题。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号