This study focus on the interruption capability of the DC circuit breaker employing a current commutation approach and evaluates the two main factors that determine the success rate for breaker current interruption, namely the current slope di/dt before current zero and the rate of rise of the transient recovery voltage dv/dt across the mechanical breaker contacts after current zero. A vacuum circuit breaker is used to evaluate DC breaker characteristics. Detailed mathematical and graphical analysis are presented for the proposed circuit operation used in analysing the circuit breaker properties, with simulation and experimental results at fault current levels up to 330 A.
机译:这项研究的重点是采用电流换向方法的直流断路器的中断能力,并评估了决定断路器电流中断成功率的两个主要因素,即电流零之前的电流斜率di / dt和电流的上升率。电流为零后,机械断路器触点上的瞬态恢复电压dv / dt。真空断路器用于评估直流断路器的特性。针对用于分析断路器特性的拟议电路操作,提供了详细的数学和图形分析,并在故障电流水平高达330 A的情况下提供了仿真和实验结果。