摘要

This paper presents a high speed current differential implementation approach for smart dc distribution systems capable of sub-millisecond fault detection. The approach utilizes the natural characteristics of dc differential current measurements to significantly reduce fault detection times compared to standard applications and hence meet requirements for dc converter protection (around 2ms). Analysis is first developed to help quantify protection implementation challenges for a given dc system. Options for implementing the proposed technique are then illustrated. Results of scaled hardware testing are presented which validate the overall protection operating times in a low voltage environment. These results show the implementation approach can consistently achieve protection system operating within the order of a few microseconds.
机译:本文提出了一种用于具有亚毫秒级故障检测能力的智能直流配电系统的高速电流差分实现方法。该方法利用了直流差分电流测量的自然特性,与标准应用相比,大大减少了故障检测时间,因此满足了对直流转换器保护的要求(约2ms)。首先开发分析是为了帮助量化给定直流系统的保护实施挑战。然后说明用于实现所提出的技术的选项。给出了按比例缩放的硬件测试结果,这些结果验证了低压环境下的总保护工作时间。这些结果表明,该实施方法可以在几微秒的数量级内一致地实现保护系统的运行。