首页> 外文OA文献 >A study on cooling characteristics of ICT equipment and cooling performance in a data center
【2h】

A study on cooling characteristics of ICT equipment and cooling performance in a data center

机译:数据中心ICT设备的散热特性和散热性能研究

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

In the work reported here, we investigated the items listed below to identify factors that affect the ICT machine air intake temperature, focusing on the effects of machine cooling characteristics on air conditioning efficiency. 1)We created a machine cooling model that relates the temperatures in different parts, derived the parameters that affect the machine air intake temperature, and analyzed the factors that govern the machine cooling characteristics. 2)To understand the factors that affect the air intake temperature of rackmounted machines that generate high heat, we conducted experiments on the relation of the machine mounting method and the air intake temperature for various amounts of air conditioning in-flow. 3)We presented a method for determining the amount of air conditioning inflow that takes machine cooling characteristics into account, and evaluated the effect of machines cooling characteristics on air conditioning efficiency.
机译:在这里报告的工作中,我们调查了以下项目,以找出影响ICT机器进气温度的因素,重点是机器冷却特性对空调效率的影响。 1)我们创建了一个机器冷却模型,该模型将不同部分的温度相关联,得出了影响机器进气温度的参数,并分析了控制机器冷却特性的因素。 2)为了了解影响产生高热量的机架式机器的进气温度的因素,我们针对各种流量的空调设备进行了机器安装方法与进气温度之间关系的实验。 3)我们提出了一种考虑到机器冷却特性的空调流入量的确定方法,并评估了机器冷却特性对空调效率的影响。