The performance of water-based fire suppression systems is governed by the dispersion of the droplets in the spray. Characterization of the spray is essential for predicting and evaluating the performance of these suppression systems. The accuracy of the spray characterization is quite sensitive to the initial spray specification when using particle tracking method to model spray dispersion. An atomization model based on first principles has been developed for predicting the distributed properties for the initial spray. Inputs to this model include injector geometry, operating conditions, and suppressant fluid properties. This modeling approach has also been integrated with drop dispersion models in FDS 4.0 to characterize spray dispersion behavior. The effect of initial spray specification on spray dispersion behavior in a quiescent environment has also been addressed. The drop size predictions using the proposed atomization model have demonstrated favorable agreement with actual sprinkler spray measurements over a range of operating conditions.
机译:水基灭火系统的性能取决于喷雾中液滴的分散。喷雾的特性对于预测和评估这些抑制系统的性能至关重要。当使用粒子跟踪方法对喷雾分散度进行建模时,喷雾表征的准确性对初始喷雾规格非常敏感。已经开发了基于第一原理的雾化模型,用于预测初始喷雾的分布特性。该模型的输入包括喷油器的几何形状,运行条件​​和抑制剂流体特性。这种建模方法也已与FDS 4.0中的液滴分散模型集成在一起,以表征喷雾分散行为。还解决了初始喷雾规范对静态环境中喷雾分散行为的影响。使用所提出的雾化模型进行的液滴尺寸预测已证明在一定范围的操作条件下与实际洒水量的测量结果吻合良好。