首页> 外文OA文献 >Airborne infection in a fully air-conditioned hospital. II. Transfer of airborne particles between rooms resulting from the movement of air from one room to another.
【2h】

Airborne infection in a fully air-conditioned hospital. II. Transfer of airborne particles between rooms resulting from the movement of air from one room to another.

机译:在配备了空调的医院中进行空气传播的感染。二。空气从一个房间移动到另一房间导致空气传播颗粒在房间之间转移。

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

Experiments were conducted simultaneously with gas and particle tracers to determine the relative loss of particles between source and recipient sites in the hospital ward units. The magnitude of this loss could be accounted for by the assumption of sedimentation from well-mixed air masses during the time required for movement between source and recipients sites. As a consequence of this loss the degree of isolation between patient rooms for airborne particles was between 4 and 25 times greater than that for gaseous contamination, which reflects the actual transport of air between the rooms. The design and construction of portable spinning-disk particle generators suitable for field studies is discussed.
机译:同时使用气体和颗粒示踪剂进行了实验,以确定医院病房单元中源点和接收点之间颗粒的相对损失。这种损失的严重程度可以通过假设在源头和接收者地点之间移动所需的时间内来自充分混合的空气团的沉降来解释。由于这种损失,患者房间之间的空气传播颗粒隔离度比气体污染隔离度高4至25倍,这反映了房间之间实际的空气传输。讨论了适用于现场研究的便携式纺丝圆盘颗粒发生器的设计和构造。