The reliability of a power system network depends greatly on the performance of the protection system. Improving the reliability of the protection scheme of the transmission lines will enhance the overall reliability of the power system network. The focus of this paper is the improvement of the reliability of a power system transmission line using fault tree analysis (FTA). The paper considers the development of fault tree diagrams for the protection scheme of the 150km-long 132-kV transmission line in Northern Nigeria. The existing protection scheme is analyzed and compared with a proposed scheme equipped with a redundancy arrangement. And the result shows that the new scheme offers significant improvement (about 51%) in the availability of the line.
机译:电力系统网络的可靠性在很大程度上取决于保护系统的性能。改善传输线保护方案的可靠性将提高电力系统网络的整体可靠性。本文的重点是使用故障树分析(FTA)改善电力系统传输线的可靠性。本文考虑了尼日利亚北部150公里长132 kV输电线路保护方案的故障树图的开发。分析了现有的保护方案,并将其与配备冗余装置的建议方案进行比较。结果表明,新方案在生产线可用性方面提供了显着改善(约51%)。