Application of ultrasonic clamp-on flow meters for in situ tests of billing meters in district heating systems

机译:超声波钳式流量计在区域供热系统计费仪表的现场测试中的应用

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

Three methods of using ultrasonic flow meters for the purpose of testing small- and medium-sized billing flow meters in district heating subscriber stations in situ were investigated. Four subscriber stations, six billing flow meters, and three ultrasonic clamp-on meters were part of the investigation. The obtained results show that clamp-on meters have measurement accuracy problems on the ordinary steel piping in the subscriber stations. When using well defined pipes mounted in series with the billing flow meters the results are clearly better; provided that the flow rates exceed a Reynolds number of approximately 10 000. In this flow region, billing flow meter deviations >±5% can be detected. A flow rate below this Reynolds number renders the method less reliable. The useful flow range is extended when using calibration data from the clamp-on meter to correct the measured data, making it possible to determine deviations >±10% in flow rates below a Reynolds number of 10 000. The investigation also showed that not all clamp-on meters are suited for this type of in situ test.
机译:研究了三种使用超声波流量计在现场供热用户站中测试中小型计费流量计的方法。四个用户站,六个计费流量计和三个超声波钳形表是调查的一部分。所得结果表明,夹钳式仪表在用户站的普通钢管上存在测量精度问题。当使用与计费流量计串联安装的定义明确的管道时,结果明显更好;前提是流量超过了约1​​0000的雷诺数。在此流量区域中,可以检测出计费流量计偏差>±5%。低于此雷诺数的流速会使该方法不可靠。当使用钳形表的校准数据来校正测量数据时,有用的流量范围得到了扩展,从而有可能确定低于雷诺数10000的流量偏差>±10%。调查还表明,并非全部钳形表适用于这种原位测试。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
代理获取

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号