An investigation on the improvement of the operation of Tenom Pangi HPP cooling power system

机译:Tenom Pangi HPP冷却电源系统运行改进的研究

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

Tenom Pangi Hydro Power Plant (HPP) is the mosteconomical power plant for Sabah Electricity Sdn. Bhd.(SESB) and also the largest hydro station in Sabah, Malaysiawith installed capacity of 3 units of 22 MW each. Due todegrading river water quality, the previous duplex strainers orfilters with manual backwash of the plant cooling watersystem (CWS) were not practically efficient to remove theaccumulated trash load. The cause of the repeatable failurefrom the substituted auto-backwash strainers was thoroughlyinvestigated, and it was found that the failure was due to thetrapped trash and/or the sediment trapped in the autobackwashfilters which ultimately clogged the filter discharge.Several technical solutions were proposed to rectify theproblem, but the open canal with auto-strainer system was the optimum solution. The canal solution was selected base on the system reliability, cost benefit, and future water quality of Padas River. Analytical and CFD solution using commercial CFD software were used to design the system. The open canal with auto-strainer system was installed and it was found that a significant amount of sediment and trash have been separated from the river water. This dramatically improves the operational reliability of the station cooling water system while maintains sufficient water flow rate and pressures.
机译:Tenom Pangi水力发电厂(HPP)是沙巴电力有限公司最经济的发电厂。 (SESB)也是马来西亚沙巴州最大的水电站,装机容量为3台,每台22兆瓦。由于河水水质下降,以前的带有手动反冲洗装置的冷却水系统(CWS)的双联过滤器或过滤器在去除累积的垃圾负荷上实际上没有效率。彻底调查了替换后的自动反冲洗滤网可重复发生的故障的原因,发现故障是由于杂质和/或自动反冲洗过滤器中截留的沉积物最终堵塞了过滤器排放造成的。提出了几种技术解决方案来纠正问题,但带自动过滤器系统的开放式运河是最佳解决方案。选择运河解决方案的依据是系统的可靠性,成本效益以及帕达斯河的未来水质。使用商业CFD软件的分析和CFD解决方案用于设计系统。安装了带有自动滤网系统的开放式运河,结果发现已经从河水中分离出了大量的沉积物和垃圾。这可以显着提高站冷却水系统的运行可靠性,同时保持足够的水流量和压力。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号