A measurements-based electrical method for locating partial discharges (PD) in transformers is described in the paper. This location method relies on the series resonance frequencies of the signals produced at the transformer terminals by a discharge on the winding. Based on the equivalent circuit of plain disc type winding which consists of series inductance (L), series capacitance (K) and shunt capacitance to earth (C) of the winding, an analytical location algorithm is derived which gives the relationship between the location of a discharge and its terminal response's series resonance frequencies. LKC parameters of the equivalent circuit can be estimated using the series resonance frequencies of a calibration signal measured at the bushing tap during PD calibration. The PD location algorithm was tested on 11 kV transformer winding using signals produced by a discharge simulator and real discharges, and the results confirm its validity with a location accuracy of better than 10% of the winding length. However, blind area where this location algorithm is not applicable does exist near the neutral of the winding and far away from the measuring terminal. Since this location algorithm uses the series resonance frequencies below 500 kHz, it can be implemented with conventional PD measuring circuitry and instruments to detect and locate discharges in power transformers.
机译:本文介绍了一种基于测量的电气方法,用于定位变压器中的局部放电(PD)。这种定位方法依赖于绕组上的放电在变压器端子上产生的信号的串联谐振频率。基于平盘式绕组的等效电路,该电路由绕组的串联电感(L),串联电容(K)和对地并联电容(C)组成,推导了解析定位算法,给出了绕组位置之间的关系。放电及其终端响应的串联谐振频率。可以使用PD校准期间在套管抽头处测得的校准信号的串联谐振频率来估算等效电路的LKC参数。 PD定位算法在11 kV变压器绕组上使用了放电模拟器产生的信号和实际放电进行了测试,结果证实了其有效性,其定位精度优于绕组长度的10%。但是,这种位置算法不适用的盲区确实存在于绕组的中性点附近,并且远离测量端子。由于此定位算法使用低于500 kHz的串联谐振频率,因此可以使用常规的PD测量电路和仪器来实现,以检测和定位电力变压器中的放电。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
代理获取

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号