Consideration of Multi-Phase Criterion in the Differential Protection Algorithm for High-Impedance Grounded Synchronous Generators

机译:高阻抗接地同步发电机差动保护算法中多相判据的考虑

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

The generator differential protection is one of the most important electrical protections of synchronous generator stator windings. Its operation principle is based on the comparison of the input current and output current at each phase winding. Unwanted trip commands are usually caused by CT saturation, wrong CT selection, or the fact that they may come from different manufacturers. In generators grounded through high impedance, only phase-to-phase or three-phase faults can be detected by the differential protection. This kind of fault causes differential current to flow in, at least, two phases of the winding. Several cases of unwanted trip commands caused by the appearance of differential current in only one phase of the generator have been reported. In this paper multi-phase criterion is proposed for generator differential protection algorithm when applied to high impedance grounded generators.
机译:发电机差动保护是同步发电机定子绕组最重要的电气保护之一。其工作原理基于每个相绕组上输入电流和输出电流的比较。不必要的跳闸命令通常是由于CT饱和,CT选择错误或它们可能来自不同的制造商而引起的。在通过高阻抗接地的发电机中,差动保护只能检测到相间或三相故障。这种故障会导致差动电流至少流入绕组的两相。据报道,仅在发电机的一相中出现了由差动电流引起的不希望的跳闸命令的几种情况。本文提出了一种适用于高阻抗接地发电机的发电机差动保护算法的多相判据。