Analysis of the types of defects and the degradation modes in different insulation materials of highvoltage (HV) electrical systems has shown that the presence of partial discharges (PD) is a very common characteristic in all of them. Once PD activity is detected, the identification and localization of the associated type of defect is very important to evaluate whether the discharges are harmful or not. During the last two decades, different approaches have been developed and applied to PD measurement and processing techniques to deal with the most common problems arising in on-site and on-line measurements, such as: high levels of background noise, appearance of interferences, simultaneous presence of different PD sources and the difficulty of locating the site of the defects and to identify them. This paper proposes a measuring method together with the implementation of three signal processing tools in order to overcome all these difficulties that appear in on-site and on-line tests. The measuring method has been implemented to evaluate in an on-site practical experience the insulation condition of the power equipment in a GIS substation. After the application of the method, important insulation defects were detected, identified and localized, on time to avoid uncontrolled failures in the electrical system of the substation under test.
机译:对高压(HV)电子系统的不同绝缘材料中的缺陷类型和退化模式的分析表明,局部放电(PD)的存在是所有这些中非常普遍的特征。一旦检测到PD活性,对缺陷相关类型的识别和定位对于评估放电是否有害非常重要。在过去的二十年中,已经开发出不同的方法并将其应用于PD测量和处理技术,以解决现场和在线测量中出现的最常见问题,例如:高背景噪音,干扰的出现,同时存在不同的PD来源,并且很难找到缺陷的位置并进行识别。本文提出了一种测量方法以及三种信号处理工具的实现,以克服现场和在线测试中出现的所有这些困难。已经实施了该测量方法,以在现场实践经验中评估GIS变电站中电力设备的绝缘状况。应用该方法后,应及时检测,识别和定位重要的绝缘缺陷,以避免被测变电站的电气系统出现无法控制的故障。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
代理获取

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号