首页> 外文OA文献 >ANALISIS GANGGUAN HUBUNG SINGKAT PADA SISTEM TENAGA LISTRIK DI PT. PERTAMINA REFINERY UNIT (RU) VI BALONGAN MENGGUNAKAN SOFTWARE ETAP 7.5.0
【2h】

ANALISIS GANGGUAN HUBUNG SINGKAT PADA SISTEM TENAGA LISTRIK DI PT. PERTAMINA REFINERY UNIT (RU) VI BALONGAN MENGGUNAKAN SOFTWARE ETAP 7.5.0

机译:PT中电力系统的短暂分布异常分析。使用ETAP软件7.5.0的PERTAMINA精炼厂(RU)VI BALONGAN

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

Penelitian ini dilakukan untuk mengetahui kemungkinan-kemungkinan yang terjadi pada gangguan arus hubung singkat di busbar 20 kV, 3,15 kV, dan 0,42 kV. Mengetahui nilai-nilai gangguan arus hubung singkat di busbar 20 kV, 3,15 kV dan 0,42 kV dengan menggunakan simulasi program software ETAP 7.5.0 dan menggunakan perhitungan manual. Mengetahui jenis gangguan arus hubung singkat manakah yang memiliki gangguan terbesar dan terkecil. Dan perhitungan manakah yang memiliki kinerja lebih cepat dan tepat. Setelah dilakukan analisis gangguan arus hubung singkat, kemungkinan yang terjadi setelah diberikan gangguan pada busbar ternyata beberapa CB/ pemutus tenaga tiba-tiba putus/ trip, karena CB merupakan peralatan yang dapat digunakan untuk memutuskan atau menghubungkan arus listrik sesuai dengan kapasitas ratingnya. Semakin jauh jarak saluran dari pusat pembangkit maka semakin besar pula hasil gangguan arus hubung singkat tersebut. Salah satu contohnya yaitu pada gangguan arus hubung singkat 3 fasa pada gangguan di busbar 20 kV yaitu sebesar 17,751 kA, di busbar 3,15 kV yaitu sebesar 22,213 kA dan di busbar 0,42 kV yaitu sebesar 40,478 kA. Jenis gangguan arus hubung singkat terbesar terdapat pada jenis gangguan arus hubung singkat 3 fasa. Dan jenis gangguan arus hubung singkat terkecil terdapat pada jenis gangguan arus hubung singkat fasa ke tanah. Dengan demikian dapat disimpulkan bahwa perhitungan program software ETAP 7.5.0 memiliki tingkat ketelitian lebih tinggi, lebih cepat dan tepat dibandingkan dengan menggunakan perhitungan manual.udThis study was conducted to determine the possibilities that occur in the short-circuit current interruption in 20 kV busbar, 3,15 kV, and 0,42 kV. Knowing values of short circuit current interruption in busbar 20kV 3,15kV and 0,42 kV by using simulation program ETAP 7.5.0 and manual calculation. Knowing types of short circuit current interruption which has the largest and smallest disturbance. which calculation and has a faster and more precise performance. After analyzing the short circuit current interruption, the possibility of which occurred after given disturbance on busbar apparently some circuit breaker suddenly dropped, since CB is an equipment that can be used to connect or disconnected the electric current in accordance with the rating capacity. The farther of distance from the center line, the greater of power interruption results of short-circuit. One example is the current noise 3-phase short circuit on the interference at 20KV busbar amount 17,751 kA, in busbar 3,15 kV amount 22,213 kA and in busbar 0,42 kV amount 40,478 kA. Type of short circuit current present in most types of interference 3-phase short-circuit. And types of disorders are the smallest short-circuit on the type of disorder phase short circuit to ground. It can be concluded that the calculation of software program ETAP 7.5.0 have a higher level of accuracy, faster and more accurate than using a manual calculation.
机译:进行这项研究以确定在20 kV,3.15 kV和0.42 kV母线中发生短路电流干扰的可能性。使用ETAP 7.5.0软件仿真程序并使用手动计算,了解母线20 kV,3.15 kV和0.42 kV上的短路电流干扰值。了解哪种类型的短路电流故障具有最大和最小的故障。以及哪些计算具有更快,更精确的性能。在分析短路电流扰动之后,母线受到扰动后发生的可能性证明某些CB /电源断路器突然断开/跳闸,因为CB是一种可用于根据其额定容量断开或连接电流的设备。通道与电厂之间的距离越远,短路电流干扰的结果就越大。一个示例是三相短路电流中断,其中20 kV母线中断为17,751 kA,3.15 kV母线为22,213 kA,0.42 kV母线为40,478 kA。三相短路电流故障类型是最大的短路电流干扰类型。在对地故障的短路电流类型中,短路电流干扰的类型最小。因此可以得出结论,与使用手动计算相比,ETAP 7.5.0软件程序的计算具有更高的准确性,更快和更精确的水平,这项研究旨在确定20 kV母线短路电流中断发生的可能性,3.15 kV和0.42 kV。通过使用仿真程序ETAP 7.5.0和手动计算,了解20kV 3.15kV和0.42 kV母线中的短路电流中断值。知道具有最大和最小扰动的短路电流中断的类型。从而计算并具有更快,更精确的性能。在分析短路电流中断之后,母线给定的干扰后发生故障的可能性显然是某些断路器突然掉落的,因为CB是一种可用于根据额定容量连接或断开电流的设备。距中心线的距离越远,短路的电源中断结果就越大。一个例子是在20KV母线量为17,751 kA,在3,15 kV母线量为22,213 kA和在0.42 kV母线量为40,478 kA时的干扰的电流噪声三相短路。大多数类型的干扰三相短路中都存在短路电流。并且无序类型是最小的短路类型,对地短路是无序类型。可以得出结论,与使用手动计算相比,ETAP 7.5.0软件程序的计算具有更高的准确性,更快和更准确的水平。

著录项

  • 作者

    Destiani Puspa Lita;

  • 作者单位
  • 年度 2014
  • 总页数
  • 原文格式 PDF
  • 正文语种 en
  • 中图分类

相似文献

  • 外文文献
  • 中文文献
  • 专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号