Technical Note: Upstream vs. Downstream Placement of FANS Device to Determine Ventilation Fan Performance in Situ

机译:技术说明:FANS设备的上游和下游位置确定原位通风风扇的性能

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

Accurate ventilation rate (VR) data are essential to maximizing the quality of aerial emission measurements. The Fan Assessment Numeration System (FANS) has been widely used by U.S. researchers in measuring aerial emissions from mechanically ventilated livestock and poultry facilities. The FANS device is used to measure airflow rates of ventilation fans in situ, thereby developing fan performance curves under field conditions. The FANS device was originally intended to be placed upstream of the fan to be calibrated. However, certain field situations make it impractical to apply the FANS device as such. This study was conducted to assess use of the FANS device downstream of a ventilation fan, with the gaps between the FANS device and the discharge cone of the exhaust fan sealed using a non-permeable fabric. Nine exhaust fans (1.22 or 1.32 m diameter) in laying hen and turkey houses were tested with the FANS device placed upstream and downstream for a building static pressure range of 10 to 40 Pa. The results revealed that downstream placement of the FANS device yielded 0.6% ±0.4% to 4.0% ±0.9 % (mean ±SE) higher but not significantly different (P u3e 0.28) VR values as compared to upstream placement for the exhaust fans tested. This magnitude of discrepancy is considered acceptable for in situ measurement of fan performance.
机译:准确的通风率(VR)数据对于最大程度地提高空气排放测量的质量至关重要。风扇评估计算系统(FANS)已被美国研究人员广泛用于测量机械通风的牲畜和家禽设施的空气排放。 FANS设备用于现场测量通风风扇的气流速率,从而在现场条件下绘制风扇性能曲线。 FANS设备最初打算放置在要校准的风扇的上游。但是,某些现场情况使得如此应用FANS设备不切实际。进行这项研究的目的是评估通风机下游的FANS装置的使用情况,FANS装置与排气扇的排气锥之间的间隙用非渗透性织物密封。在FANS设备位于上游和下游的静态压力范围为10至40 Pa的情况下,对9个蛋鸡和火鸡舍的排气扇(直径为1.22或1.32 m)进行了测试。结果表明,在FANS设备的下游放置产生0.6与测试的排气风扇的上游位置相比,VR值高%±0.4%到4.0%±0.9%(平均±SE),但无显着差异(P±0.28)。对于风扇性能的现场测量,这种差异程度被认为是可以接受的。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号