Evaluation of power line cable fatigue parameters based on measurements on a laboratory cable test span

机译:根据实验室电缆测试跨度上的测量值评估电源线电缆的疲劳参数

摘要

The present paper describes experiments carried out on IREQ laboratory cable test bench. Test span arrangement is a 63.15m cable span with termination ends designed so as to minimize energy dissipation. A shaker provides a vertical alternating force to the conductor. During the experiments, a maximum of information on mode shape is collected: location of nodes, antinode amplitude of vibration, relative displacement at 44.5, 89, and 178mm from the last point of contact with the metallic clamp. Several configurations are studied: span equipped with an homogeneous steel cable, span equipped with an ACSR Crow conductor, sometimes in combination with other equipments such as a vibration damper or a local mass, to investigate how the presence of such devices impacts conductor vibrations. It results from these experiments an interesting comparison of two widely used fatigue indicators, the relative displacement Yb 2 (also called “bending amplitude”) and fymax (the product of antinode amplitude of vibration by frequency). Also, collected data gives indirect information on conductor variable bending stiffness.
机译:本文介绍了在IREQ实验室电缆测试台上进行的实验。测试跨度是63.15m的电缆跨度,其末端设计为最大程度地减少了能量消耗。振动器向导体提供垂直交变力。在实验过程中,最多收集了有关模态形状的信息:节点的位置,振动的波腹振幅,距与金属夹的最后接触点44.5、89和178mm的相对位移。研究了几种配置:配备均匀钢缆的跨度,配备ACSR Crow导体的跨度,有时与诸如减振器或局部质量之类的其他设备结合使用,以研究此类设备的存在如何影响导体振动。从这些实验中得出的结果是,对两个广泛使用的疲劳指标进行了有趣的比较,相对位移Yb 2(也称为“弯曲幅度”)和fymax(振动的波腹振幅与频率的乘积)。另外,收集的数据还提供了有关导体可变弯曲刚度的间接信息。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号