首页> 外文OA文献 >Lithium bromide high-temperature absorption heat pump. Coefficient of performance and exergetic efficiency
【2h】

Lithium bromide high-temperature absorption heat pump. Coefficient of performance and exergetic efficiency

机译:溴化锂高温吸收式热泵。绩效系数和精力充沛的效率

摘要

A theoretical study on the employment of a lithium bromide absorption heat pump in Spain, used as machine type I and aimed to produce heat at 120°C via waste heat sources at 60°C, is given in the paper. Real performance conditions are stated for each component of the machine, namely the absorber, the heat recoverer, the generator, the condenser, the solution pump, the expansion valve and the evaporator. By means of thermodynamic diagrams (p, t, x) and (h, x), the required data are obtained for calculation of the heat recovered in the evaporator Qe, and the heat delivered to the absorber Qa and to the condenser Qc, as well as the heat supplied to the generator Qg. In addition, the heat delivered by the hot solution to the cold solution in the heat recovered Qr, and the work Wp done by the solution pump are calculated. The probable COP is calculated, and values are obtained close to 1.4. The working temperature in the generator is determined; it ranges from 178 to 200°C. © 1990
机译:本文对在西班牙使用溴化锂吸收式热泵(作为I型机器)的理论研究进行了研究,旨在通过60°C的废热源在120°C产生热量。对于机器的每个组件,即吸收器,热回收器,发电机,冷凝器,溶液泵,膨胀阀和蒸发器,都规定了实际的性能条件。借助于热力学图(p,t,x)和(h,x),获得所需的数据,以计算在蒸发器Qe中回收的热量,以及传递到吸收器Qa和冷凝器Qc的热量。以及提供给发电机Qg的热量。另外,计算在热回收Qr中由热溶液传递给冷溶液的热量,以及由溶液泵完成的功Wp。计算可能的COP,并获得接近1.4的值。确定发电机的工作温度;温度范围为178至200°C。 ©1990

著录项

  • 作者

    Izquierdo M.; Aroca S.;

  • 作者单位
  • 年度 2014
  • 总页数
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类

相似文献

  • 外文文献
  • 中文文献
  • 专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号