Compensation in nonsinusoidal, unbalanced three-phase four-wire systems with active power-line conditioner

机译:具有有源电力线调节器的非正弦,不平衡三相四线制系统中的补偿

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

For three-phase four-wire circuits, two compensation criteria have been established: one based on the instantaneous value concept and the other on the average value concept. Thus, according to the instantaneous value concept the non instantaneous power current is reduced, without altering the instantaneous active power. According to the average value concept, the nonactive average-current is reduced, without altering the average power. When the zero-sequence voltage component exists, both compensation types would not enable the zero-sequence (neutral) source current elimination. Then, two approaches are marked in this paper. The first one is for eliminating the non instantaneous power current or the nonactive average-current but the neutral current can still flow. The second one for eliminating the modified non instantaneous power current or the modified nonactive average-current, thus the neutral current component is compensated. According to recent recommendations in this work three-phase systems are considered as four-conductor systems. Experimental results are obtained to confirm the theoretical properties and to show the compensator performance.
机译:对于三相四线电路,已经建立了两个补偿标准:一个基于瞬时值概念,另一个基于平均值概念。因此,根据瞬时值概念,在不改变瞬时有功功率的情况下减小了非瞬时功率电流。根据平均值概念,可以在不改变平均功率的情况下减少无源平均电流。当存在零序电压分量时,两种补偿类型均无法消除零序(中性)电源电流。然后,本文标记了两种方法。第一个用于消除非瞬时功率电流或非有功平均电流,但中性电流仍然可以流动。第二个用于消除修改的非瞬时功率电流或修改的非有效平均电流,从而补偿零线电流分量。根据这项工作中的最新建议,三相系统被认为是四导体系统。获得了实验结果,以确认理论特性并显示补偿器性能。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
代理获取

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号