Analysis of the Voltage and Current Unbalances in a Closed-loop Distribution Feeder Caused by Removal of a Failed Capacitor Unit

机译:拆除故障电容器单元导致闭环配电馈线中电压和电流不平衡的分析

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

[[abstract]]The main purpose of this paper is to analyze the voltage and current unbalances in a closed-loop distribution feeder caused by removal of a failed capacitor unit in an ungrounded Y-connected capacitor bank with one series group per phase. The distribution feeder unbalance as a result of the removal of one failed capacitor unit by its fuse is usually unexpected and unmanageable due to the poor environment. Distribution engineers should pay more attention to this situation to lessen its impact on the system and equipment. A sample feeder with closed-loop arrangement was used to simulate a practical feeder under normal and abnormal operation conditions, which a failed capacitor unit is removed. The simulation results indicate that the removal of a failed capacitor bank may significantly impact the system operation if the capacitor bank has only one series group. The outcomes are of value to distribution engineers to thoroughly realize the effects of the removal of a failed capacitor bank.
机译:[[摘要]]本文的主要目的是分析由于每相有一个串联组的未接地Y型连接的电容器组中的故障电容器单元的移除而导致的闭环配电馈线中的电压和电流不平衡。由于恶劣的环境,分配馈线由于其保险丝卸下了一个失效的电容器单元而造成的不平衡通常是无法预料的,​​并且无法解决。配电工程师应更加注意这种情况,以减少其对系统和设备的影响。使用具有闭环布置的样品进料器来模拟在正常和异常操作条件下的实际进料器,该故障进料器可以将出现故障的电容器单元移除。仿真结果表明,如果电容器组只有一个串联组,则去除故障的电容器组可能会严重影响系统运行。这些结果对配电工程师来说是非常有价值的,它可以使他们彻底了解拆除故障电容器组的效果。

著录项

  • 作者

    Huang Wei-Tzer;

  • 作者单位
  • 年度 2012
  • 总页数
  • 原文格式 PDF
  • 正文语种 en
  • 中图分类

相似文献

  • 外文文献
  • 中文文献
  • 专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号