The purpose of this paper is to present the results obtained in the first two years of operation of the grid-connected photovoltaic (PV) systems installed in the named “Solar XXI” building. One PV system, made with multicrystalline silicon modules, has a peak power of 12 kW and was installed on the façade; another system made with amorphous silicon modules has a peak power of 6 kW and was installed in the surrounding park area near the building. From 1st February 2006 until 31 July 2008, the measured daily average, of the building electrical energy consumption, was about 75 kWh and the two PV systems produced in average about 72 % of this energy. The averaged measured Performance Ratio of the systems was about 0.84 for the PV Façade and about 0.76 for the PV in the Park.
机译:本文的目的是介绍安装在名为“ Solar XXI”建筑物中的并网光伏(PV)系统在运行的头两年中获得的结果。一种由多晶硅模块制成的光伏系统的峰值功率为12 kW,并安装在立面上。另一种由非晶硅模块制成的系统的峰值功率为6 kW,安装在建筑物附近的公园区域中。从2006年2月1日到2008年7月31日,每天测得的建筑电能平均消耗量约为75 kWh,两个光伏系统平均产生了约72%的电能。在公园内,系统的平均实测性能比对于PV立面约为0.84,对于PV约为0.76。