Reducing Building Energy Costs Using Optimized Operation Strategies for Constant Volume Air Handling Systems

机译:使用恒定体积空气处理系统的优化运行策略降低建筑物能源成本

摘要

Building energy consumption can be substantiallyreduced after implementing what we call ExtendedO&M Measures. The Extended O&M Measures are ascientific refinement of traditional O&M measures.Specifically, they involve resetting the cooling deck orheating deck temperature according to the ambienttemperature such that maximum energy efficiency canbe achieved without compromising indoor air qualityand comfort. Extended O&M Measures optimizesystem performance as a whole rather than focusing onthe malfunction of individual component. Our studyinvolving five medical and institutional buildings atthe University of Texas Medical Branch (UTMB).Galveston shows that Extended O&M Measures canreduce chilled water and condensate costs by$517,800/yr or 19% of the total building energy cost($2.7 million dollars). This potential percentagesavings is comparable to the LoanSTAR measuredthermal energy savings in 10 buildings at anotherUniversity of Texas campus where constant air volumesystems have been converted to variable volumesystems. Though in the later case fan electricityconsumption is also reduced but with some investmentcost. On the other hand, Extended O&M Measures donot require any retrofit or investment cost. ExtendedO&M Measures have been implemented in one of thefive buildings, and the measured savings are consistentwith predicted savings. It seems that the ExtendedO&M Measures are an excellent alternative toconverting constant volume systems to variablevolume systems, especially if there are no retrofit funds available.
机译:在实施我们所谓的ExtendedO&M措施后,可以大大降低建筑能耗。扩展运维措施是对传统运维措施的科学改进,具体包括根据环境温度重置冷却甲板或加热甲板温度,从而在不损害室内空气质量和舒适性的前提下实现最大的能源效率。扩展的运维措施可从整体上优化系统性能,而不是着眼于单个组件的故障。我们的研究涉及得克萨斯大学医学分校(UTMB)的五栋医疗和机构建筑物,加尔维斯顿研究表明,扩展的O&M措施可以使冷水和冷凝水成本每年减少517,800美元,占建筑能源总成本(270万美元)的19%。该潜在的节省百分比可与LoanSTAR在德克萨斯大学另一校区的10座建筑物中测得的热能节省相媲美,该大学的恒定风量系统已转换为可变风量系统。尽管在后一种情况下,风扇的耗电量也减少了,但是投资成本却很高。另一方面,扩展的O&M措施不需要任何改造或投资成本。已在五座建筑物之一中实施了扩展的O&M措施,所测得的节余与预期节余相符。看起来,ExtendedO&M措施是将恒定容量系统转换为可变容量系统的绝佳选择,尤其是在没有可用的翻新资金的情况下。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号