Impacts of Optimized Cold Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation

机译:优化的冷热甲板复位时间表对双风道VAV系统的影响-理论和模型仿真

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

Optimal hot and cold deck reset schedulescan decrease simultaneous heating and coolingin VAV AHUs comparing with constant colddeck temperature operation. In this paper,optimization models are developed. The energyimpacts are simulated for a typical officebuilding in the hot and humid climate(Galveston, Texas).The simulation results show that theoptimized reset schedules can reduce the cost ofAHU energy consumption (cooling, heating andfan power) by 8% to 20% in normal VAVsystems when the minimum air flow rateincreased from 30% to 70% of the maximumflow.
机译:与恒定的甲板温度运行相比,最佳的冷热板重置时间表可以减少VAV AHU的同时加热和冷却。本文开发了优化模型。针对典型办公场所在炎热潮湿的气候条件下(德克萨斯州加尔维斯顿)的能耗影响进行了仿真,仿真结果表明,优化的重置计划可以将AHU能耗(制冷,供暖和风扇电源)的成本降低8%至20%当最小空气流量从最大流量的30%增加到70%时的VAV系统。