Optimal Outside Air Control for Air Handling Units with Humidity Control

机译:带湿度控制的空气处理机组的最佳外部空气控制

摘要

Most air handling units (AHUs) in commercial buildings have the (air) economizer cycle to use outside air for free cooling under certain outside air conditions. Ideally the economizer cycle is enabled if outside air enthalpy is less than return air enthalpy. During the economizer cycle, outside air flow is modulated to seek mixed air temperature at a supply air temperature set point. Since the outside air may be dry during the economizer cycle, humidification is required for AHUs with humidity control. As a result, the economizer cycle saves cooling energy but requires excessive steam for humidification. Therefore the economizer cycle may not be economical. An optimal outside air control method is developed to minimize the total cost of mechanical cooling and steam humidification. The impacts of chilled water price, steam price, and space minimum humidity set point are analyzed. Finally the optimal outside air control zones are presented on a psychrometric chart under differential energy price ratios and minimum indoor humidity set points.
机译:商业建筑中的大多数空气处理机组(AHU)都有(空气)节能器循环,可以在一定的外部空气条件下使用外部空气进行免费冷却。理想情况下,如果外部空气焓小于返回空气焓,则启用节能循环。在省煤器循环期间,调节​​外部空气流量以在送风温度设定点寻找混合空气温度。由于在省煤器循环期间外部空气可能会变干,因此具有湿度控制的AHU需要加湿。结果,省煤器循环节省了冷却能量,但需要过多的蒸汽来加湿。因此,节能器循环可能不经济。开发了一种最佳的外部空气控制方法,以最大程度地减少机械冷却和蒸汽加湿的总成本。分析了冷冻水价格,蒸汽价格和空间最小湿度设定点的影响。最后,在不同的能源价格比和最小室内湿度设定点下的干湿图上显示了最佳的外部空气控制区域。

著录项

  • 作者

    Wang G.; Liu M.;

  • 作者单位
  • 年度 2006
  • 总页数
  • 原文格式 PDF
  • 正文语种 en_US
  • 中图分类

相似文献

  • 外文文献
  • 中文文献
  • 专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号