首页> 外文OA文献 >Performance Test and Energy Saving Analysis of a Heat Pipe Dehumidifier
【2h】

Performance Test and Energy Saving Analysis of a Heat Pipe Dehumidifier

机译:热管除湿机性能测试与节能分析

摘要

Heat pipe technology applied to ventilation, dryness, and cooling and heating radiator in a building is introduced in this paper. A new kind of heat pipe dehumidifier is designed and tested. The energy-saving ratio with the heat pipe dehumidifier ranges from 11.81% to 30.34% compared with the normal dehumidifier, according to the performance testing. The dehumidification capacity and the surface cooler power increases, but the energy saving ratio is reduced with the increase of air relative humidity, dry bulb temperature and air quantity
机译:介绍了应用于建筑物通风,干燥,冷暖气片的热管技术。设计并测试了一种新型的热管除湿机。根据性能测试,与常规除湿机相比,热管除湿机的节能率在11.81%至30.34%之间。除湿能力和表面冷却器功率增加,但是节能率随着空气相对湿度,干球温度和空气量的增加而降低

著录项

  • 作者

    Zhao X.; Li Q.; Yun C.;

  • 作者单位
  • 年度 2006
  • 总页数
  • 原文格式 PDF
  • 正文语种 en_US
  • 中图分类

相似文献

  • 外文文献
  • 中文文献
  • 专利