Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions

机译:静压设定水平对HVAC能耗和室内条件的影响

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

Air static pressure must be maintained at acertain level leaving the air-handing unit (AHU) toforce a suitable amount of air through the terminalboxes. However, an excessive static pressure level isoften used due to ( 1 ) lack of a control device in aconstant volume system (CV); (2) malfunctioningcontrol device in a variable volume (VAV) system;and (3) fear of failure to maintain room temperature.High static pressure often develops excessive damperleakage in older mixing boxes. This results in aninappropriate mixing of hot and cold air and anexcessive amount of air entering the space.Consequently, the actual fan power, heating andcooling energy consumption all become significantlyhigher than the design values. Even worse, the systemmay not be able to maintain room conditions due tounwanted simultaneous heating and cooling, and maybe noisy due to the excessive static pressure. Thispaper proposes to control the hot duct pressure andthe Variable Frequency Drives ( VFD's) to controlthe fan static i.e. the cold duct pressure. Both atheoretical analysis and a case study results arepresented in this paper.
机译:必须将空气静压保持在一定水平,以离开空气处理单元(AHU),以迫使适量的空气通过接线盒。然而,由于(1)在恒定容积系统(CV)中缺少控制装置,经常会使用过高的静压水平; (2)可变容量(VAV)系统中的控制装置发生故障;以及(3)担心无法维持室温。高静压通常会在较旧的搅拌箱中产生过多的阻尼泄漏。这会导致冷热空气混合不当,以及过多的空气进入空间,因此,实际的风扇功率,加热和冷却能耗都大大高于设计值。更糟糕的是,由于不必要的同时加热和冷却,系统可能无法维持室内条件,并且由于过大的静压而可能产生噪音。本文提出了控制热风道压力和变频驱动器(VFD's)来控制风扇的静态压力,即冷风道压力。本文同时进行了理论分析和案例研究。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号