The Effect of Reduced Evaporator Air Flow on the Performance of a Residential Central Air Conditioner

机译:蒸发器空气流量减少对住宅中央空调性能的影响

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

This paper discusses the measured degradation in performance of a residential air conditioning system operating under reduced evaporator air flow. Experiments were conducted using a R-22 three-ton split-type cooling system with a short-tube orifice expansion device. Results are presented here for a series of tests in which the evaporator air flow was reduced from 25 to 90% below what is normally recommended for this air conditioner.At present, very little information is available which quantifies the performance of a residential cooling system operating under degraded conditions such as reduced evaporator air flow. Degraded performance measurements can provide information which could help electric utilities evaluate the potential impact of system-wide maintenance programs.
机译:本文讨论了在蒸发器气流减少的情况下运行的住宅空调系统的性能下降。使用带有短管孔口膨胀装置的R-22三吨分体式冷却系统进行实验。这里给出了一系列测试的结果,这些测试中蒸发器的空气流量从通常推荐的水平降低了25%至90%。目前,很少有信息可以量化住宅制冷系统的性能在退化的条件下,例如蒸发器气流减少。降级的性能测量可以提供信息,可以帮助电力公司评估系统范围维护计划的潜在影响。