Measured Effects of Retrofits - A Refrigerant Oil Additive and a Condenser Spray Device - On the Cooling Performance of a Heat Pump

机译:改造的实测效果-冷冻机油添加剂和冷凝器喷雾装置-对热泵冷却性能的影响

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

A 15-year old, 3-ton single package air-to-air heat pumpwas tested in laboratory environmental chamberssimulating indoor and outdoor conditions. Afterdocumenting initial performance, the unit was retrofittedwith a prototype condenser water-spray device andretested. Results at standard AM cooling ratingconditions (95?F outdoor dry bulb and 80167 OF indoordry bulb/wet bulb temperatures) showed the capacityincreased by about 7%, and the electric power demanddropped by about 8%, resulting in a steady-state EERincrease of 17%. Suction and discharge pressures werereduced by 7 and 37 psi, respectively.A refrigerant oil additive formulated to enhancerefrigerant-side heat transfer was added at a dose of oneounce per ton of rated capacity. and the unit was testedfor several days at the same 95?F outdoor conditions andshowed essentially no increase in capacity, and a slight3% increase in steady-state EER. Adding more additivelowered the EER slightly. Suction and dischargepressures were essentially unchanged.Our short-term testing showed that the condenser-spraydevice was effective in increasing the cooling capacityand lowering the electrical demand on an old andrelatively inefficient heat pump, but the refrigerantadditive had little effect on the cooling performance ofour unit Sprayer issues to be resolved include the effectof a sprayer on a new, high-efficiency air conditioner/heatpump, reliable long-term operation, and economics.
机译:在模拟室内和室外条件的实验室环境室内对一个15岁,3吨重的单包装空气对空气热泵进行了测试。在记录初始性能之后,对该单元进行了原型冷凝水喷淋装置的改装,并进行了重新测试。在标准AM冷却额定条件下(95?F室外干球和80167室内干球/湿球温度)的结果显示,容量增加了约7%,电力需求下降了约8%,导致稳态EER增加了17 %。吸气和排气压力分别降低了7 psi和37 psi。以每吨额定容量1盎司的剂量添加了配制用于增强制冷剂侧传热的制冷剂油。并在相同的95?F室外条件下对该装置进行了几天的测试,结果表明容量基本没有增加,稳态EER略微增加了3%。添加更多的添加剂会稍微降低EER。短期测试表明,冷凝器喷雾装置可以有效地提高冷却能力并降低旧的效率相对较低的热泵的电力需求,但制冷剂添加剂对我们喷雾器的冷却性能影响很小要解决的问题包括喷雾器对新型高效空调/热泵的影响,可靠的长期运行以及经济性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号