摘要

Based on the case research for China's first central air conditioning system utilizing natural cool river water as chilled water, this paper analyzes the technical design-and-innovation process and operating characteristics of Fan-Coil Units (FCUs) in the system. An approximate formula is proposed for computing the cooling capacity of FCUs when the temperature of water supply is a little higher than designed temperature. Finally, recommendations are given for the design of the FCUs to follow dry operating conditions in the air conditioning system that directly utilize natural cool resources.
机译:本文以中国第一套以自然冷河水为冷冻水的中央空调系统为例,分析了系统中风机盘管的技术设计,创新过程和运行特性。当供水温度略高于设计温度时,提出了一个近似公式来计算FCU的冷却能力。最后,对FCU的设计提出了建议,以遵循直接利用自然冷却资源的空调系统中的干燥运行条件。