首页> 外文OA文献 >Impacts of Water Loop Management on Simultaneous Heating and Cooling in Coupled Control Air Handling Units
【2h】

Impacts of Water Loop Management on Simultaneous Heating and Cooling in Coupled Control Air Handling Units

机译:水循环管理对耦合控制空气处理机组同时供热和供冷的影响

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

The impacts of the water loop managementon the heating and cooling energy consumptionare investigated by using model simulation. Thesimulation results show that the total thermalenergy consumption can be increased by 24%for a typical AHU in San Antonio, Texas whenthe differential pressure is increased from 7 psito 21 psi for both chilled water and hot waterloops. It appears that significant amounts ofenergy consumption can be reduced byimproving the differential pressure of waterloops. This paper presents the system model,methods, and the results.
机译:通过模型仿真研究了水循环管理对供热和制冷能耗的影响。仿真结果表明,当冷水和热水回路的压差从7 psi增加到21 psi时,在德克萨斯州圣安东尼奥市的典型AHU的总热能消耗可增加24%。似乎可以通过改善水环的压差来减少大量的能源消耗。本文介绍了系统模型,方法和结果。