Fire and Life Safety Analysis of The Performing Arts Center's Christopher Cohan Center

机译:表演艺术中心克里斯托弗科汉中心的消防和生命安全分析

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

This report is a review of the fire protection systems installed in the Christopher Cohan Center on the Cal Poly, San Luis Obispo campus. The systems reviewed are the passive structural fire protection, passive and active egress components, and active detection and suppression systems. The report examines whether the reviewed systems in the building meet the prescriptive requirements of the 2010 California Building Code(CBC) and California Fire Code(CFC). The building will be further subjected to a performance based analysis. Two design fire scenarios are presented, and an analysis of available safe egress time (ASET) is compared with an analysis of the required safe egress time (RSET). Fire Safety Goals Five goals found in building guides such as NFPA 5000 and the SFPE Performance Based Design guides are as follows: 1. “Provide life safety for the public, building occupants, and emergency responders by minimizing firerelated injuries and preventing undue loss of life. 2. Minimize damage to property and cultural resources from fire. 3. Provide for continuity of operations. Minimize undue loss of operations and business-related revenue caused by fire-related damage. 4. Limit the environmental impact of fire from combustion products and release of hazardous materials.” 5. Limit the fire-related damage to buildings and objects of historical and/or cultural significance. The performance section of this report will focus only on the life safety goal as applied to the building occupants. The prescriptive part of the report will determine if the building is compliant with the 2010 CBC and CFC, with respect to fire and egress related systems. If it is, then the first goal is assumed to have been achieved to a degree equivalent to a new building built to prescriptive code with respect to those systems. The report will not address the remaining goals beyond the following: Survey of construction documents to this point have not revealed systems for managing sprinkler discharge or other fire-related environmental hazard mitigation systems. The building is an existing structure without a protected historical status, so goal 5 does not apply.
机译:本报告是对Cal Poly,San Luis Obispo Campus的Cal Chather Wohan中心安装的防火系统的审查。审查的系统是被动结构防火,被动和有源出口组件,以及主动检测和抑制系统。该报告探讨了建筑中审查的系统是否符合2010年加州建筑码(CBC)和加利福尼亚州消防码(CFC)的规定要求。该建筑物将进一步遵循基于性能的分析。提出了两个设计火灾情景,并将可用的安全出口时间(ASET)分析与所需的安全出口时间(RSET)进行比较。消防安全目标在建筑指南中发现的五个目标,如NFPA 5000和SFPE性能的设计指南如下:1。“通过最大限度地减少壁炉般的伤害并防止过度丧失生活,为公众,建筑物和应急响应者提供生命安全。 2.最大限度地减少火灾对财产和文化资源的损害。 3.提供操作的连续性。最大限度地减少对与火灾相关损伤引起的业务和业务相关收入的不当损失。 4.限制火灾燃烧产品的环境影响和危险材料的释放。“ 5.将与历史和/或文化意义的建筑物和对象限制有关的火灾损坏。本报告的绩效部分仅关注适用于建筑物的生命安全目标。报告的规定部分将确定建筑物是否符合2010年CBC和CFC,关于火灾和出口相关系统。如果是,则假设第一个目标已经实现到相当于相对于这些系统的规范性代码构建的新建筑物的程度。该报告将不会解决以下其余目标:施工文件的调查尚未透露用于管理喷水灭火或其他与火灾相关的环境危害缓解系统的系统。该建筑物是现有结构,没有受保护的历史状态,因此目标5不适用。

著录项

  • 作者

    David Phillips;

  • 作者单位
  • 年度 -1
  • 总页数
  • 原文格式 PDF
  • 正文语种
  • 中图分类

相似文献

  • 外文文献
  • 中文文献
  • 专利
代理获取

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号