首页> 外文OA文献 >Analysis of Transient Voltage Stability in a Low Voltage Distribution Network Using SST for the Integration of Distributed Generations
【2h】

Analysis of Transient Voltage Stability in a Low Voltage Distribution Network Using SST for the Integration of Distributed Generations

机译:SST用于分布代代集成的低压配电网瞬态电压稳定性分析

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

Models of a low voltage distribution network using a typical tertiary-structure solid state transformer (SST) for the integration of distributed generations (DGs) and a conventional low voltage distribution network integrated with DGs were established to study the transient voltage stability issue, using the power system simulation software PSCAD. Effects on the transient voltage stability of the load bus and DC bus in the SST system are analyzed when grid-side cable line faults (such as short circuit and line disconnection) occur or the total output of DGs drops greatly. The results show that, comparing with the conventional system, the SST has apparent advantages on enhancing the transient voltage stability of load bus while facing different disturbances, even though SST has to regulate the voltage passively. Short circuit faults at different location of the grid-side line have different effects on the transient voltage stability, while the effect of disconnection fault is not related to fault location. Moreover, the DC bus voltage is easy to keep climbing continually when short circuit fault of the line occurs that is close to the SST input stage or disconnection fault occurs at any location of the line. If a battery energy storage station is installed, the transient voltage stability of DC bus and load bus will be improved effectively because of the regulation function of battery storage.
机译:建立了使用典型的三级结构固态变压器(SST)的低压分布网络的模型,用于集成分布式代代(DGS)和集成与DGS的传统低压分布网络,以研究瞬态电压稳定性问题,使用电力系统仿真软件PSCAD。当电网侧电缆线故障(如短路和线断线)发生或DGS的总输出大大时,分析了SST系统中负载总线和DC总线的瞬态电压稳定性的影响。结果表明,与传统系统相比,SST对增强负载总线的瞬态电压稳定性的同时面对不同的干扰,即使SST必须被动地调节电压,SST也具有明显的优点。在网格侧线的不同位置的短路故障对瞬态电压稳定性产生不同的影响,而断开故障的效果与故障位置无关。此外,当线路发生靠近SST输入级或断开故障时,直流母线电压易于继续攀爬,靠近SST输入级或断开故障发生在线的任何位置。如果安装了电池储能站,则由于电池存储的调节功能,将有效地提高直流总线和负载总线的瞬态电压稳定性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
代理获取

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号