首页> 外文OA文献 >Performance evaluation of FKM central unit air condition system/chilled water system
【2h】

Performance evaluation of FKM central unit air condition system/chilled water system

机译:FKM中央空调/冷水系统性能评估

摘要

Air conditioning system has been introduced in past several decades in order to serve comfort condition to the humans. Air conditioner is defined as control air movement, temperature, humidity and cleanliness in a needed space. Meanwhile chilled water is to control the movement of water, air, fluid flow and temperature from chiller plant room. There are several types of system where hot air can be removed from a system in the process of refrigeration and air conditioning. Basic air-conditioning systems and chilled water covers four main components including compressor, condenser, throttling valve and evaporator. The process of heat removal can be done by heat transfer directly or indirectly. Since the system been introduced, performance of the system will be the main issues and until now there are many researches still ongoing in order to get the best performance of air conditioning system. Faculty of Mechanical engineering (FKM) in Pekan has started its operation in July 2009 and almost building in the faculty is occupied with air conditioning system. The type of air conditioning system in the faculty is central unit air conditioning system. The performance of the air conditioning system in the faculty becomes an interesting part to be studied to those who are in that field. An informal interview was conducted with officials from the Jabatan Pembangunan dan Pengurusan Harta (JPPH) that is responsible for monitoring this air conditioning system. The problem that arises in the central air conditioning system in the FKM are influences JPPH to cooperate in order to help an individual for analyzing the performance of air conditioning system.The objective of this project is to review the working system and analyze the performance of air conditioners and chilled water system for daily use. In addition, evaluation and review of cooling load is also taken into account for two rooms, specifically name by Computer Lab and Excellent Centre. The heat gain analysis is compulsory conducted in order to estimate performance of central unit air conditioning system. The heat gain for the Computer Lab and Excellent Centre is calculated to be 23.297kW and 39.952kW respectively. Different condition of date were taken and been analyzed which is performances of the system using single chiller running alternately and two chiller running simultaneously. The result shows that when the system is being operated with single chiller simultaneously, the total available cooling capacity can be ranging between 770kW to 810kW. Whereas for two chiller operations, the total available cooling capacity by the chiller is 1246.77kW. The room total load capacity with single chiller in operation alternately, the value load capacity for Computer Lab is ranging from 18.072kW to 20.482kW and for Excellent Centre is 26.746kW to 27.981kW. While for two chiller operations simultaneously, the room total load capacity for Computer Lab is 25.301kW and for Excellent Centre is 42.168kW. It can be conclude that air conditioning system running with single chiller operation is not enough to absorb the heat gain in the particular room in the present of study. Therefore, the system with 2 chiller operation is the best to meet the needs and more systematic guide for the consumer at Faculty of Mechanical Engineering (FKM) in Pekan. Study also emphasizes the relationship between temperature, pressure, flow rate, the amount of cooling and performance of work for each component and total components involved.
机译:在过去的几十年中已经引入了空调系统,以便为人类提供舒适的条件。空调被定义为控制所需空间中的空气流动,温度,湿度和清洁度。同时,冷冻水是控制冷冻机房中水,空气,流体流量和温度的运动。在制冷和空调过程中,有几种类型的系统可以从系统中排出热风。基本的空调系统和冷冻水涵盖了四个主要组件,包括压缩机,冷凝器,节流阀和蒸发器。排热过程可以通过直接或间接传热来完成。自从引入系统以来,系统的性能将成为主要问题,直到现在,为了获得最佳性能的空调系统,仍在进行许多研究。北干的机械工程学院(FKM)于2009年7月开始运营,该学院的几乎所有建筑物都装有空调系统。学院的空调系统类型为中央单元空调系统。教员中空调系统的性能已成为该领域人员研究的有趣部分。与Jabatan Pembangunan dan Pengurusan Harta(JPPH)的官员进行了非正式采访,该官员负责监控该空调系统。 FKM中央空调系统中出现的问题是影响JPPH合作以帮助个人分析空调系统的性能。该项目的目的是审查工作系统并分析空气的性能。日常使用的空调和冷冻水系统。此外,还考虑了两个房间的冷却负荷评估和审查,这两个房间由计算机实验室和卓越中心专门命名。为了估计中央空调系统的性能,必须进行热增益分析。计算得出的计算机实验室和卓越中心的热量分别为23.297kW和39.952kW。采取了不同的日期条件并进行了分析,这是使用单个制冷机交替运行而两个制冷机同时运行的系统性能。结果表明,当系统同时使用单个冷却器运行时,总可用冷却能力可能在770kW至810kW之间。对于两个制冷机操作,该制冷机的总可用制冷量为1246.77kW。交替运行单个冷水机组的房间总负荷能力,计算机实验室的总负荷能力为18.072kW至20.482kW,卓越中心的负荷能力为26.746kW至27.981kW。对于两个制冷机同时运行,计算机实验室的房间总负载容量为25.301kW,卓越中心的房间总负载容量为42.168kW。可以得出结论,在目前的研究中,以单个制冷机运行的空调系统不足以吸收特定房间的热量吸收。因此,在北根机械工程学院(FKM),具有2个制冷机运行的系统是满足需求的最佳方法,也是对用户的更系统的指南。研究还强调了温度,压力,流量,冷却量和每个组件和涉及的组件的工作性能之间的关系。

著录项

  • 作者

    Amir Hamzah Azahar;

  • 作者单位
  • 年度 2010
  • 总页数
  • 原文格式 PDF
  • 正文语种
  • 中图分类

相似文献

  • 外文文献
  • 中文文献
  • 专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号