首页> 外文OA文献 >Fault Development in Wet, Low Voltage, Oil-Impregnated Paper Insulated Cables
【2h】

Fault Development in Wet, Low Voltage, Oil-Impregnated Paper Insulated Cables

机译:湿,低压,油浸纸绝缘电缆的故障开发

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

Few studies have been carried out on the failure processes of low voltage distribution cables. This is mainly due to their excellent track record of high reliability, and their use of traditional technologies. Growing quantities of aged cable within the network now make management of these assets an important issue. This paper describes measurements of leakage current, partial discharges and arc formation within 400 V oil-impregnated paper insulated cable structures which have been artificially wetted by immersion in bulk water. A generic picture is produced to show the gradual evolution from a leakage current through discharge growth to final catastrophic failure. Rapid changes to the core temperature of a wet cable are shown to produce transient, high levels of leakage current. It is also shown that by increasing the core temperature more slowly these high levels can be reduced. It is suggested that the characteristics of individual arcs within successive half cycles may provide a basis for predicting whether an incipient fault will lead to failure in the short term. © 2008 IEEE.
机译:很少有研究已经进行了低压配电电缆的破坏过程进行。这主要是由于高可靠性的优良记录,他们使用传统的技术。内网老化电缆的数量不断增加,现在让这些资产的一个重要问题的管理。本文描述了泄漏电流的测量,部分放电和已经由浸没在大体积的水人工润湿400 V油浸渍纸绝缘电缆结构内形成电弧。一个通用的图象中产生以显示从一个漏电流通过放电生长逐步演变到最终灾难性故障。到湿电缆的芯温度急剧变化被示为产生短暂,高含量的泄漏电流。它也表明,通过增加芯温度更慢这些高含量可被降低。有人建议,连续的半周期内的各个圆弧的特性可以用于预测早期故障是否会导致失败在短期内提供一个基础。 ©2008 IEEE。

著录项

  • 作者

    Simon Rowland; Miao Wang;

  • 作者单位
  • 年度 2008
  • 总页数
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类

相似文献

  • 外文文献
  • 中文文献
  • 专利
代理获取

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号