首页> 外文OA文献 >Long-term evaluation of HVDC transmission line audible noise and its correlation with background noise
【2h】

Long-term evaluation of HVDC transmission line audible noise and its correlation with background noise

机译:HVDC传输线的长期评估声音噪声及其与背景噪声的相关性

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

The audible noise (AN) generated by corona discharge from a full-scale, high-voltage direct-current (HVDC) transmission line was evaluated over a one-year period from December 2017 to November 2018. The double bipolar HVDC transmission line using a metallic return conductor was demonstrated using a full-scale tower having a height of 21 m in Gochang, Korea. The measured AN in an outdoor environment was statistically evaluated and compared in different seasons and weather conditions. The A-weighted spectrum of the HVDC corona noise exhibited a greater distribution than the background noise above 1.0 kHz in the frequency domain. Various background noises were considered and eliminated to improve the measurement accuracy. The highest AN levels were exhibited during the spring season. Individuals in the age range of 18–60 years were randomly selected to conduct a human-perception test. The results indicated that 15% of the participants became aware of the AN from the corona discharge when it was >5 dBA greater than the background noise. The AN was <36 dBA when the conductor surface gradient was <18 kV/cm with a six-bundle sub-conductor.
机译:通过电晕放电从全刻度产生的可听见的噪声(AN),高压直流(HVDC)传输线,评价在1年期间从2017年12至11月2018使用双双极HVDC传输线路金属回路导体,使用具有21微米的高敞,韩国的高度的满量程塔证实。在室外环境中所测量的AN进行统计学评估,并在不同的季节和天气条件相比较。高压直流电晕噪声的A-加权谱表现出比上述在频域中1.0千赫的背景噪声较大的分布。各种背景噪声被认为是和消除,以提高测量精度。最高AN水平在春季展出。在18-60岁年龄范围内的个体,随机选定进行的人类感知的测试。结果表明,参与者的15%才知道原来AN从电晕放电时,它是> 5分贝大于背景噪声。的AN是<36分贝当导体表面梯度为<18千伏/厘米具有六束分导体。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
代理获取

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号