首页> 外文OA文献 >NUMERICAL MODELLING OF POWERHOUSE STRUCTURE STRESS-STRAIN STATE CAUSED BY UNEQUAL SETTLEMENT AND DURING ITS LEVELLING OPERATIONS
【2h】

NUMERICAL MODELLING OF POWERHOUSE STRUCTURE STRESS-STRAIN STATE CAUSED BY UNEQUAL SETTLEMENT AND DURING ITS LEVELLING OPERATIONS

机译:不平等结算引起的强电场结构应力 - 应力状态的数值模型及其平整运算

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

Reinforced concrete elements of the Zagorsk-2 pumped storage station structure had got into unexpected stress-strain state after unequal settlement and bending of the structure crosswise of the flow as a result. Cracks emerged in the load bearing reinforced concrete elements and the reinforcement crossing the cracks suffered significant tensile stresses. Important to mention, that the main reinforcement is arranged along the flow. There was a cofferdam designed and constructed across the reverse channel, which allowed to decreasethe water level and remove water from the channel to provide stabilized position of the powerhouse. After stabilization of the powerhouse, it was planned to level the powerhouse by the compensation grouting method.Based on the finite element soil-structure model of the powerhouse, the stress-strain state of reinforced concrete elements subject to unequal settlement and during the levelling operations was determined.The results of the stress-strain state analysis were compared with the actual in-situ stress data obtained by the “reinforcement de-stressing” method. According to the results of the analysis, it is necessary to strengthen the RC load bearing structures of the Zagorsk-2 powerhouse.In the article, the main design proposals for strengthening the RC load bearing structures of the Zagorsk-2 powerhouseby the external carbon fibre reinforcement are given and justified.
机译:Zagorsk-2泵送存储站结构的钢筋混凝土元件在不平等的沉降和弯曲的横向横向的情况下达到意外的应力 - 应变状态。结果。在负载钢筋混凝土元件中出现的裂缝以及穿过裂缝的加强件遭受了显着的拉伸应力。重要的是提及,主要加强沿着流量排列。围绕反向通道设计和构造的围堰,其允许减少水位并从通道中去除水以提供能量稳定的位置。经过稳定的强国后,计划通过补偿灌浆方法水平。基于省电的有限元土结构模型,钢筋混凝土元件的应力 - 应变状态,经受不平等的结算和在平衡运作期间确定了应力 - 应变状态分析的结果与通过“增强抗应力”方法获得的实际原位应力数据进行了比较。根据分析结果,有必要加强Zagorsk-2厂房的RC承载结构。在本文中,主要设计提案,用于加强外部碳纤维的Zagorsk-2动力率的RC承载结构加强并合理。

著录项

  • 作者

    A.V. Aleksandrov;

  • 作者单位
  • 年度 2018
  • 总页数
  • 原文格式 PDF
  • 正文语种 rus;eng
  • 中图分类

相似文献

  • 外文文献
  • 中文文献
  • 专利
代理获取

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号