首页> 外文OA文献 >Base Isolation for Seismic Retrofitting of a Multiple Building Structure: Design, Construction, and Assessment
【2h】

Base Isolation for Seismic Retrofitting of a Multiple Building Structure: Design, Construction, and Assessment

机译:用于多层建筑结构的地震改装的基础隔离:设计,建设和评估

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

The paper deals with the seismic retrofit of a multiple building structure belonging to the Hospital Centre of Avellino (Italy). At first, the paper presents the preliminary investigations, the in situ measurements and laboratory tests, and the seismic assessment of the existing fixed-base structures. Having studied different strategies, base isolation proved to be the more appropriate, also for the possibility offered by the geometry of the building to easily create an isolation interface at the ground level. The paper presents the design project, the construction process, and the details of the isolation intervention. Some specific issues of base isolation for seismic retrofitting of multiple building structures were lightened. Finally, the seismic assessment of the base-isolated building was carried out. The seismic response was evaluated through nonlinear time-history analysis, using the well-known Bouc-Wen model as the constitutive law of the isolation bearings. For reliable dynamic analyses, a suite of natural accelerograms compatible with acceleration spectra of Italian Code was first selected and then applied along both horizontal directions. The results were finally used to address some of the critical issues of the seismic response of the base-isolated multiple building structure: accidental torsional effects and potential poundings during strong earthquakes.
机译:本文涉及属于Avellino(意大利)的医院中心的多层建筑结构的地震改造。首先,本文提出了初步调查,原位测量和实验室测试,以及现有固定基础结构的地震评估。研究了不同的策略,基本隔离被证明是更合适的,也是由于建筑物几何形状提供的可能性,以便在地面级别轻松创建隔离界面。本文提出了设计项目,施工过程和隔离干预的细节。多层建筑结构的地震改装的碱隔离的一些特定问题被减轻。最后,进行了基地建筑物的地震评估。通过非线性时间历史分析评估地震反应,使用众所周知的BOUC-WEN模型作为隔离轴承的本构规律。为了可靠的动态分析,首先选择一套与意大利代码的加速度谱兼容的自然加速仪套件,然后沿水平方向施加。结果最终用于解决基本隔离的多层建筑结构的地震反应的一些关键问题:在强大的地震期间意外扭转效应和潜在的冲击。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
代理获取

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号