Futaleufú hydropower plant has 4 Francis turbines rated 118 MW and it is connected to the power system by 2x330 kV lines. Studies carried out in the past did not predict the instable operation of Futaleufú after a 330 kV line fault, when some Futaleufú turbines are automatically disconnected as a consequence of the faulted line tripping. Load rejection caused by disconnected turbines generate large transients in the remaining turbines due to hydraulic coupling through the common conduits. Then, to improve related models and, therefore, to improve studies results of such a line fault it was necessary to make several tests in Futaleufú power plant. Finally, these models were used to conduct studies to design a new automatism, like the gate partial closing of the remaining turbines, to obtain a dynamically stable operation of Futaleufú after the disconnection by fault of a line of 330 kilovolts.
机译:Futalefú水电站有4辆班轮涡轮机Rated 118 MW,它通过2x330 kV线连接到电力系统。在过去进行的研究没有预测Futaleufú在330 kV线路故障后的不稳定运行,当由于故障线跳闸时,一些Futaleufuf涡轮机自动断开连接。由于通过公共导管,由断开的涡轮机引起的负载抑制在剩余的涡轮机中产生大的瞬变。然后,为了改善相关模型,因此,改善了这种线路故障的研究结果,有必要在Futaleufú发电厂进行多次测试。最后,这些模型用于开展研究以设计一种新的自动化,如剩余涡轮机的栅极部分关闭,以在断开330千伏的断线后获得Futaleufú的动态稳定运行。