Experimental Investigation of an Environmental Control Unit Utilizing Carbon Dioxide for Heating and Cooling

机译:利用二氧化碳加热和冷却的环境控制装置的试验研究

摘要

This report details the tests performed on R22 box and R744 breadboard versions of the US ArmyEnvironmental Control Unit (ECU) with a nominal cooling capacity of 9,000 BTU/hr (0.75 Tons or 2.64 kW). AnR22 ECU box currently used by the Army was tested and used as the baseline for comparison with the later R744testing. This baseline system is generally used where portable air conditioning is needed in the field; the box is alsoequipped with electric resistance heaters. The baseline box was found to outperform its rated capacity. An R744system was tested in a breadboard format, this system was comprised of components similar to what would be usedin an ECU box if it were converted from R22. This breadboard system was capable of operating as both an airconditioner and as a heat pump. A cooling COP approximately equal to the box system was attained with thebreadboard. The breadboard did provide a HPF greater than unity for all heat pump tests, making it is more efficientthan the electric resistance heaters found in the box system. Detailed comparisons were made between several R744heat exchangers in different orientations under varying operating conditions. Evaporators were tested in horizontaland vertical tube orientations. The flat top fin evaporator was found to work well in both horizontal and verticalorientations. The round top fin evaporator, which may have contained a manufacturing defect, performed muchbetter with the tubes vertical, than with the tubes horizontal. Overall the best heat exchanger was the round top finevaporator with the tubes vertical; however this heat exchanger performed the worst with the tubes horizontal. In airconditioning mode, both gas coolers performed similarly. In heat pump mode, the six-port tube heat gas coolerperformed better in almost every regard in comparison to the four-port tube with the only exception being the airside pressure drop.
机译:该报告详细介绍了在标称制冷量为9,000 BTU /小时(0.75吨或2.64千瓦)的美国陆军环境控制单元(ECU)的R22箱型和R744面包板版本上进行的测试。测试了陆军目前使用的AnR22 ECU盒,并将其用作与以后的R744测试进行比较的基准。该基准系统通常用于现场需要便携式空调的地方;盒子里还装有电阻加热器。发现基准框的性能超出其额定容量。 R744系统以面包板格式进行了测试,该系统包含的组件与从R22转换而来的ECU盒中使用的组件相似。该面包板系统既可以用作空调,也可以用作热泵。用面包板达到近似等于箱式系统的冷却COP。面包板在所有热泵测试中确实提供了大于1的HPF,使其比盒式系统中的电阻加热器更高效。在不同的运行条件下,在不同方向上的几个R744热交换器之间进行了详细的比较。蒸发器在水平和垂直管方向上进行了测试。发现平顶翅片蒸发器在水平和垂直方向上都能很好地工作。圆形翅片蒸发器可能存在制造缺陷,在垂直放置的情况下比水平放置的情况要好得多。总的来说,最好的热交换器是圆管式细蒸发器,其管子垂直。但是,这种热交换器在水平管的情况下表现最差。在空调模式下,两个气体冷却器的性能相似。在热泵模式下,六通管式热气冷却器在所有方面均比四通管更好,唯一的例外是空气侧压降。

著录项

  • 作者

    Wujek S.S.; Hrnjak P.S.;

  • 作者单位
  • 年度 2006
  • 总页数
  • 原文格式 PDF
  • 正文语种 {"code":"en","name":"English","id":9}
  • 中图分类

相似文献

  • 外文文献
  • 中文文献
  • 专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号