首页> 美国政府科技报告 >Prestressed Concrete Pipe Failure Jordan Aqueduct, Reach 3
【24h】

Prestressed Concrete Pipe Failure Jordan Aqueduct, Reach 3

机译:预应力混凝土管道失效Jordan aqueduct,达到3

获取原文

摘要

The Bureau of Reclamation conducted failure investigations to identify thecause(s) of a catastrophic rupture of prestressed concrete pipe under impressed current cathodic protection, which occurred on Reach 3 of the Jordan Aqueduct near Salt Lake City, Utah, on August 7, 1984. The multidisciplinary analyses included corrosion, design, petrographic, structural, and metallurgical investigations. From the onset of the failure, the issue was one of reconciling cathodic overprotection and defective (longitudinally cracked) prestressing wire. The report contains a summary of the findings from Reclamation investigations.