首页> 美国政府科技报告 >Fatality Assessment and Control Evaluation (FACE) for Colorado: Foreman on Electrical Line Crew is Electrocuted When an Energized Line Contacts a Guy Wire
【24h】

Fatality Assessment and Control Evaluation (FACE) for Colorado: Foreman on Electrical Line Crew is Electrocuted When an Energized Line Contacts a Guy Wire

机译:科罗拉多州的死亡率评估和控制评估(FaCE):当一条通电线接触一条电线时,电线上的工头被电击

获取原文

摘要

On January 25, 1994 a 38-year old employee of a electrical contractor was electrocuted when an energized jumper wire contacted a guy wire onto which the deceased was holding. The deceased was a foreman of the line crew that was replacing electrical poles and rerouting electrical lines for a local rural electric association. When the incident occurred, the crew was disconnecting power lines from an old pole to allow pole replacement. The deceased had used a climbing belt and boot hooks to climb the pole; he had assisted a co-worker who was positioned in a truck-mounted insulated bucket on the opposite side of the pole. The deceased had accomplished the task for which he had ascended the pole, and was resting prior to his descent. The pole was supported in place by two guy wires, one attached approximately four inches above the other, both wrapped around the pole on metal bands and then secured in place with metal brackets. The workers were disconnecting the remaining two segments of a single-phase 7200-volt line that joined at the pole and were connected with a 'jumper wire' (an uninsulated energized wire that allows the electricity to bypass the gap in the two line segments where they attach to the pole). A 'hot hoist' (a hand-operated winch and nylon strap with end clamps that are attached to each line approximately two feet away from the pole) had been installed to pull the lines toward the pole, thus releasing tension on the sections of line at the point of connection to the pole. This allows the crew to disconnect the ends of the line from the pole. When the injury occurred, one end of the line had been disconnected. This created slack in the jumper wire. From contact marks on the jumper wire and the guy wire hooks it appeared that the jumper wire contacted the guy wire bracket. The deceased was holding onto the two guy wires and provided the path for the flow of electricity between guy wires and the ground.

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号