首页> 美国政府科技报告 >Comparison of CFAST Predictions to USCG Real-Scale Fire Tests
【24h】

Comparison of CFAST Predictions to USCG Real-Scale Fire Tests

机译:CFasT预测与UsCG实际火灾试验的比较

获取原文

摘要

The zone model CFAST was used to make predictions of single room pre-flashoverfire tests conducted in a steel enclosure. These results were then compared with previously published measurements obtained in fire tests. Tests included diesel pool fires, polyurethane slab fires, and wood crib fires. Half of these tests used natural ventilation while the remaining tests used forced ventilation. With the exception of heat release rates, all CFAST inputs were selected without knowledge of the experimental results. Key variables compared include the upper layer temperature, the hot layer interface location, and ceiling temperatures. Overall, predictions made by CFAST were in good agreement with the data. There was a general tendency to overpredict both the hot gas layer temperature and the boundary surface temperature which may be due to underprediction of boundary heat losses. Experimental results showed that heat release rates varied with ventilation configurations by as much as a factor of 3. This observation indicates that the wide practice of using free burn heat release rate data in compartment fire predictions can result in overprediction of compartment fire conditions.

著录项