首页> 美国政府科技报告 >Effect of Operation Room Geometry and Ventilation System Parameter Variations on the Protection of the Surgical Site
【24h】

Effect of Operation Room Geometry and Ventilation System Parameter Variations on the Protection of the Surgical Site

机译:手术室几何和通气系统参数变化对手术部位保护的影响

获取原文

摘要

In this study, airflow modeling and particle tracking methodologies were used to consider the effect of geometry changes--in particular, ceiling height variations--in an operating room (OR). The ceiling height of the OR was varied from 9 feet (2.74 m) to 12 feet (3.66 m) in 1 foot (0.30 m) increments, and a range of different air change rates were considered at each height--between 20 and 30 air changes per hour (ACH). The contamination of the surgical site was monitored to determine the primary effect of the geometrical and flow rate variations. The results of the study indicate that the ACH becomes an important parameter as the ceiling height is reduced. In order to explain this phenomenon, a mathematical study of the main driving forces in the room was made. In particular, a consideration was made of the Archimedes number (Ar) equation (ratio of Grashof to Reynolds numbers) in a simplified representation of the OR. The result of this consideration is that the contamination of the surgical site becomes sensitive to the value of Ar as the ceiling height is progressively reduced. A consideration of Ar is therefore recommended in the design of the ventilation system of an OR.

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com