首页> 美国政府科技报告 >Cable Response to Live Fire (CAROLFIRE). Volume 3: Test Descriptions and Analysis of Circuit Response Data
【24h】

Cable Response to Live Fire (CAROLFIRE). Volume 3: Test Descriptions and Analysis of Circuit Response Data

机译:电缆对火灾的响应(CaROLFIRE)。第3卷:电路响应数据的测试描述和分析

获取原文

摘要

This report describes a thermally-induced electrical failure (THIEF) models ability to predict the behavior of power, instrument, and control cables during a fire. The model is intended to be incorporated as a subroutine for deterministic fire models, and it is of comparable accuracy and simplicity to the activation algorithms for various other fire protection devices (e.g., sprinklers, heat and smoke detectors). THIEF model predictions are compared to experimental measurements of instrumented cables in a variety of configurations, and the results indicate that the model is an appropriate analysis tool for nuclear power plant applications. This work was performed as part of the CAROLFIRE (Cable Response to Live Fire) program sponsored by the U.S. Nuclear Regulatory Commission. The experiments for CAROLFIRE were conducted at Sandia National Laboratories, Albuquerque, New Mexico. Details of the CAROLFIRE experimental program are contained in Volumes 1 and 2 of this three-volume series.