首页> 美国政府科技报告 >T2 Laboratories, Inc., Runaway Reaction (Four Killed, 32 Injured), Investigation Report
【24h】

T2 Laboratories, Inc., Runaway Reaction (Four Killed, 32 Injured), Investigation Report

机译:T2 Laboratories,Inc。,失控反应(四人死亡,32人受伤),调查报告

获取原文

摘要

At 1:33 pm on December 19, 2007, a powerful explosion and subsequent chemical fire killed four employees and destroyed T2 Laboratories, Inc. (T2), a chemical manufacturer in Jacksonville, Florida. It injured 32, including four employees and 28 members of the public who were working in surrounding businesses. Debris from the reactor was found up to one mile away, and the explosion damaged buildings within one quarter mile of the facility. On December 19, T2 was producing its 175th batch of methylcyclopentadienyl manganese tricarbonyl (MCMT). At 1:23 pm, the process operator had an outside operator call the owners to report a cooling problem and request they return to the site. Upon their return, one of the two owners went to the control room to assist. A few minutes later, at 1:33 pm, the reactor burst and its contents exploded, killing the owner and process operator who were in the control room and two outside operators who were exiting the reactor area. The CSB found that a runaway exothermic reaction occurred during the first (metalation) step of the MCMT process. The CSB tested the T2 batch recipe to determine the most likely failure scenario. A loss of sufficient cooling during the process likely resulted in the runaway reaction, leading to an uncontrollable pressure and temperature rise in the reactor. The pressure burst the reactor; the reactors contents ignited, creating an explosion equivalent to 1,400 pounds of TNT.

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号