U.S. requirements for uncommitted nuclear installations in water scarce areas that might require dry cooling tower systems are minimal through the year 2000 (6to 23 GWe). In these areas it appears that peak-shaved dry/wet cooling systems are more attractive than all-dry tower cooling unless water costs were to approach the high level of several cents per gallon. The differential cooling system evaluated cost of peak-shaved dry/wet cooling systems above wet towers is typically $20to $30/kWe for steam turbines;whereas,dry towers can represent an incremental burden of as much as $80/kWe. Gas turbine (Brayton Cycle) systems show similar benefits from an evaporative heat sink to those for steam turbine cycles--lower cooling system evaluated costs for peak-shaved dry/wet cooling systems that for conventional wet towers. These cooling system cost differentials do not reflect total costs for Brayton Cycle gas turbine plants. Together these added costs and uncertainties may substantially exceed the dollar incentives available for development of the Brayton Cycle for power generation needs for water deficient sites.