首页> 美国政府科技报告 >Measurement of Ion Current Density at Ground Level in the Vicinity of High Voltage DC Transmission Lines
【24h】

Measurement of Ion Current Density at Ground Level in the Vicinity of High Voltage DC Transmission Lines

机译:高压直流输电线路附近地面离子电流密度的测量

获取原文

摘要

Sensors for measuring vertical current density at ground level near high voltage dc (HVDC) transmission lines are subject to error when the sensor is not in the ground plane. The magnitude of this error, for guarded and unguarded sensors, has been investigated using both dc electric fields with space charge and ac electric fields in a parallel plate facility. For conditions like those expected under HVDC transmission lines, the results obtained using ac and dc methods agreed to within experimental uncertainty. The measured errors are as large as 25 percent for guarded sensors and significantly larger for unguarded sensors. Data for various sensor elevations and guarding are presented in graphs to aid the designer.