In-Depth Survey Report: Control Technology for Ethylene Oxide Sterilization in Hospitals at St. Francis/St. George Hospital, Cincinnati, Ohio

机译:深入调查报告:圣弗朗西斯/圣保罗医院环氧乙烷灭菌控制技术。乔治医院,俄亥俄州辛辛那提市

获取原文

摘要

An in depth survey of control technology for reducing exposure during ethylene-oxide (75218) sterilization was conducted at Saint Francis/Saint George Hospital (SIC-8062), Cincinnati, Ohio, in January, 1985. Personal and area air samples were analyzed for ethylene-oxide. Engineering controls consisted of isolating the sterilizer, local exhaust ventilation above the sterilizer door and exit drain, and general ventilation. The author commends the facility for a very sound program of ethylene-oxide control. Decontamination room personnel could be at risk in case of an inadvertent release of ethylene-oxide from the sterilizer safety valve or other leaks in the sterilizer cabinet. The condition could be easily remedied by enclosing the top of the cabinet. Environmental monitoring is also recommended.